❄ Compressor Code Lookup
Home › Sullair › Power Interruption
Sullair WS Controller · Power Interruption

What does Power Interruption mean on a Sullair compressor?

Short answer: Control power was interrupted. If your Sullair WS Controller is showing Power Interruption, the controller has logged a specific, documented condition. This page covers what it means, what causes it, what you can safely fix yourself, and when — and why — it takes a technician.

What exactly is the machine telling you?

The controller detected an interruption in control power. Note that with an auto-restart timer set, the compressor may restart automatically after power returns.

Which machines show this?

Sullair's mid-range stationary rotary screws fitted with the WS controller — a text-display unit found on many shop and light-industrial packages from the 2010s. The WS names its faults in plain English (High Temperature, Separator dP High, Aux Motor Overload, Power Interruption) and uses staged temperature protection: a warning at 225 °F, a time-delayed fault at 235 °F, and an immediate trip at 255 °F. Faults are reset from the STOP key after the cause is corrected and the unit has cooled. Practical tip: if the auto-restart timer is configured, the machine can start by itself after a power interruption — make sure nobody is working near it before you walk away from a Power Interruption message.

What causes it?

  • A facility power blip or outage interrupting control power
  • Repeated interruptions from a supply or connection problem

Can you fix it yourself?

Partly — confirm the facility event and log repeat times. Mind the auto-restart: the machine can start on its own when power returns.

Step by step — what to try, in order:

  1. Check whether the facility had a power blip or outage at the fault time
  2. Verify no one is working near the machine before resetting — it can restart on its own
  3. If interruptions are frequent, log the times and check them against other equipment cycling
One reset is diagnosis, repeated resets are damage. If the same fault returns after a single reset, the underlying condition is real — stop resetting and deal with the cause.
Safety: The compressor may restart automatically after power is restored.

When do you need a technician — and why?

Control power that drops with no facility-wide outage needs an electrician to test line voltage and connections — intermittent supply faults need instruments.

When to call: Call an electrician if control power drops repeatedly with no facility-wide outage — line voltage and connections need testing.

If it does come to a service call and you're in Nashville, TN or Birmingham, AL, we maintain independently compiled lists of local companies that service industrial air compressors — real businesses with verified contact information, none of whom paid to be listed.

Related questions

What does Power Interruption mean on a Sullair WS Controller?

Control power was interrupted. The controller detected an interruption in control power. Note that with an auto-restart timer set, the compressor may restart automatically after power returns.

Can I fix Power Interruption on a Sullair WS Controller myself?

Partly — confirm the facility event and log repeat times. Mind the auto-restart: the machine can start on its own when power returns.

When does Power Interruption on a Sullair WS Controller need a technician?

Control power that drops with no facility-wide outage needs an electrician to test line voltage and connections — intermittent supply faults need instruments. Call an electrician if control power drops repeatedly with no facility-wide outage — line voltage and connections need testing.

Verified against service documentation: Sullair WS Controller documentation for Power Interruption (best-aire.com)